ZP215150000X100

EATON BLADEUPS PREASSEMBLED SYSTEM|ZP215150000X100

UPC: 743172088680
Length/Depth: in
Width: 0.0001 in
Height: 0.0001 in
Weight: 0.000100 lbs
Catalog Number: ZP215150000X100
Warranty: Eaton Selling Policy 25-000, one (1) year from the date of installation of the Product or eighteen (18) months from the date of shipment of the Product, whichever occurs first.
Compliances: CISPR22 Class A / FCC part 15 Class A, CE Marked
Certifications: cULus Listed, CSA Std. C22.2, UL 1778
Battery Quantity: 200
Battery Form Factor: Battery pack with 10 internal batteries
Battery Management: ABM technology (3-stage charging extends battery service life by 50% and provides advance warning for battery replacement)
Battery Rating: 240V/5 Ah
Extended Battery Capability: Yes, add up to four additional 3U battery enclosures>34 min at 100% load>1 hour at 50% load
Max Number of Battery Packs: 4 internal packs, 4 external EBMs per UPS module
Runtime at Full Load: 4.7 min
Battery Type: Sealed, lead-acid
Receptacle: (1) hardwired-MBM
Output Power Factor: 1.0
Output Voltage Range: 180-228 V, Ph-Ph
Output Frequency: 50/60 Hz
Topology: Online/Double-conversion
Wattage: 60 kW
VA Rating: 60 kVA
Output Waveform: Sine wave
Voltage: 208Y/120V
Number of Outputs Hardwired: 1
Input Connection: Fixed connection
Input Nominal Voltage: 208Y/120V
Input Power Factor: >0.97 with IT loads (PFC power supplies, load dependent in HE Mode)
Communication: WEB, SNMP, Modbus TCP, BacNet IP
Ethernet Interface: Yes
Expansion Slots: (4) available, 1 slot filled with Network Card
User Interface: Yes
Software Compatibility: Eaton Intelligent Power Software Suite CD (included)
Altitude: 1000m at 40°C (105°F)
BTU Rating: 2100 watts, 7160 BTU/hr (HE mode), 6000 watts, 20470 BTU/hr (Normal mode)
Temperature Range: 0°to 40°C (32°to 104°F), batteries recommended max. 25°C (77°F)
Relative Humidity: 5-95% non-condensing
Efficiency: >97% in HE mode
Surge Protection: Yes
Auto Shutdown Function: Yes
Benefit: ,
Hot Swap Power: Yes
Mounting Method: Rackmount
Nominal Frequency: 45-65 Hz
Phase Input: Three-phase
Phase Output: Three-phase
Protocol: SNMP
Type of Interface: Menu driven
Warranty Country: United States of America